Press Release (Jan 31, 2013)Status of TEPCO's Nuclear Power Stations after the Tohoku-Chihou-Taiheiyou-Oki Earthquake (Daily Report as of 3:00 PM, January 31)

Due to the Tohoku-Chihou-Taiheiyou-Oki Earthquake which occurred on March 11, 2011, TEPCO's facilities including our nuclear power stations have been severely damaged. We deeply apologize for the anxiety and inconvenience caused.
With regard to the accident at Fukushima Daiichi Nuclear Power Station, on April 17, 2011, we have compiled the roadmap towards restoration from the accident and on July 19 we accomplished the Step1 target "Radiation dose is in steady decline". Then on December 16 we confirmed the accomplishment of the Step 2 target "Release of radioactive materials is under control and radiation doses are being significantly held down".
In addition, on December 21, 2011, we have compiled the "Mid-to-long-Term Roadmap toward the Decommissioning of Fukushima Daiichi Nuclear Power Units 1-4, TEPCO".
In addition to the maintenance of the plant's stable condition, we will implement Mid-to-Long Term countermeasures towards the decommissioning of Fukushima Daiichi Nuclear Power Units 1-4 to enable evacuees to return to their homes as soon as possible and reduce the anxiety of the people in Fukushima and the whole nation as soon as possible.

Below is the status of TEPCO's nuclear power stations (Fukushima Daiichi and Fukushima Daini).

* The updates are underlined.

[Fukushima Daiichi Nuclear Power Station]
·Unit 1 to 4: Abolishment (April 19, 2012)
·Unit 5 to 6: Outage due to regular inspections before the earthquake

-At around 11:55 AM on January 19, a TEPCO employee found ground water overflowing from the drain receiver of the regular reactor water injection pump on the hill onto the ground (concrete). Since the pipeline which transfers water from the drain receiver to the buffer tank via underwater pump is not functioning properly due to some reason, it is assumed that the ground water is overflowing from the drain receiver. The area affected by leakage is approx. 2mx4mx1mm and the amount of leaked water is approx. 8L. The leaked water is being kept inside the dam using sandbags and has not flowed to the outside. The radioactivity density results of the leaked water are as follows. Cesium-134: Below the detection limit (Detection limit: 1.8x10-2Bq/cm3), Cesium-137: Below the detection limit (Detection limit: 2.1x10-2Bq/cm3), Antimony (Sb)-125: 1.5x10-1Bq/cm3. Based on these results, the leaked water is assumed to be treated water. From 1:01 to 1:08 PM, water transfer from the drain receiver to a spare tank was performed, and leakage from the drain receiver was stopped at 1:08 PM. The incident has no impact on reactor water injection. On January 30, the cause of the incident was identified to be the pipeline which transfers water from the drain receiver to the buffer tank via the underwater pump being clogged due to frozen groundwater, which disabled water transfer and resulted in groundwater overflowing from the drain receiver. Currently, groundwater is being transferred manually utilizing a backup pump which will be continued until anti-freeze measure is implemented.

-At 6:48 AM on January 30, as part of restoring Unit 1 condensate water storage tank, we started transferring the water stored in the tank to Unit 1 Waste Treatment Building. At 4:37 PM on the same day, the transfer was stopped.

[Fukushima Daini Nuclear Power Station]
·Unit 1 to 4: Shutdown due to the earthquake.

* Revised past progress

The aforementioned attachments are only available in Japanese.
We apologize for any inconvenience this may cause.

In Order to view the PDF documents, you will need a software product called Adobe® Acrobat® Reader installed on your computer. You can download this software product for free from Adobe's Web site by clicking the left button: